VoyForums Announcement: Programming and providing support for this service has been a labor of love since 1997. We are one of the few services online who values our users' privacy, and have never sold your information. We have even fought hard to defend your privacy in legal cases; however, we've done it with almost no financial support -- paying out of pocket to continue providing the service. Due to the issues imposed on us by advertisers, we also stopped hosting most ads on the forums many years ago. We hope you appreciate our efforts.

Show your support by donating any amount. (Note: We are still technically a for-profit company, so your contribution is not tax-deductible.) PayPal Acct: Feedback:

Donate to VoyForums (PayPal):

Login ] [ Contact Forum Admin ] [ Main index ] [ Post a new message ] [ Search | Check update time ]
Subject: 14/2 NM switch legs on a twenty amp branch circuit


Author:
Daniel Benoit
[ Next Thread | Previous Thread | Next Message | Previous Message ]
Date Posted: 18:01:37 04/03/05 Sun

Is it within code to use # 14 NM wire for switchlegs on a twenty amp branch circuit. (Residential setting)

[ Next Thread | Previous Thread | Next Message | Previous Message ]

Replies:
[> Subject: Re: 14/2 NM switch legs on a twenty amp branch circuit


Author:
Amos Lowrance
[ Edit | View ]

Date Posted: 07:47:42 04/05/05 Tue

>Is it within code to use # 14 NM wire for switchlegs
>on a twenty amp branch circuit. (Residential setting)
Tap conductors, which is what we are talking about, are covered in section 240.21. Looking thru this section I find no case in which this is permitted. Table 210.24 permits a #14 to be tapped from a 20 ampere circuit, however, please note that this tap is limited to a maximum of 18 inches in length by Section 210.19(A)(4) Exception No.1(c). I hope that this answers your question. If not please feel free to contact me at Lowrance_a@mail.chattanooga.gov.

[ Post a Reply to This Message ]
[> Subject: Re: 14/2 NM switch legs on a twenty amp branch circuit


Author:
John Minick, NEMA
[ Edit | View ]

Date Posted: 00:10:38 09/21/05 Wed

>Is it within code to use # 14 NM wire for switchlegs
>on a twenty amp branch circuit. (Residential setting)

The answer is maybe but probably doubtful. See NEC Section 210.3 that states, "Branch circuits recognized by this article shall be rated in accordance with the maximum permitted ampere rating or setting of the overcurent device." Thus, you have stated that the circuit overcurrent device used in the installation is 20 with the tap conductors being 14 AWG. Section 240.4(D) states, "Unless specifically permitted in 240.4(E) or 240.4(G), the overcurrent protection shall not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 ampers for 10 AWG copper" conductors. 240.4(E)(1) addresses tap conductors in 210.19(A)(4) for other loads including lighting taps. 210.19(A)((4)Exception No. 1 (a) states that individual lampholders or luminaires with taps extending not longer than 18-inches beyond any portion of the lampholder orluminaire. Also, (c) of this same section states that "individual outlets, other than receptacle outlets, with taps not over 18-inches long" shall be permitted. Thus, the limit for 14 AWG taps from 12 AWG branch circuit conductors protected at 20 amperes is 18-inches, which is probably not of adequate length for a switchleg. Also, see 240.4(G) that does not list lighting taps so (G) is no help for your question. last and not least, 240.21(A)concerning branch circuit taps refers us back to 210.19 of which we have already looked. However,one last comment, the reference in 210.19(A)(4)Exception No.1 (b) that refers to 410.67 that allows 6-foot taps from an outlet box to a luminaire could possibly be used but only where the tap conductors are properly temperature rated and where the conductors are placed in a suitable raceway or where the wiring method is Type MC or Type AC cable not more than 6-feet in length. In most cases this is not a feasible option for dwelling switchlegs. So, the answer is maybe but probably doubtful.

[ Post a Reply to This Message ]


Post a message:
This forum requires an account to post.
[ Create Account ]
[ Login ]
[ Contact Forum Admin ]


Forum timezone: GMT-5
VF Version: 3.00b, ConfDB:
Before posting please read our privacy policy.
VoyForums(tm) is a Free Service from Voyager Info-Systems.
Copyright © 1998-2019 Voyager Info-Systems. All Rights Reserved.