Date Posted: 11:22 12/23/04 Thu
Author: Phil Clark
Subject: Re: Bonding Conductor for a hydromassage bathtub
In reply to: Dave Williams 's message, "Bonding Conductor for a hydromassage bathtub" on 10:34 12/23/04 Thu

>At the December meeting there was a question during
>the code panel asking if the bonding conductor could
>be a 8 AWG stranded conductor or does it need to be a
>solid conductor. Tom Lichtenstein stated that section
>680.74 requires the conductor needs to be copper and
>not smaller than 8 AWG solid. I just wanted to get
>other thoughts.

I can't see any "gray" in this Code section. I think that the intent is to have the ampacity of a min. #8 and the structural integrity of a solid conductor

[ Next Thread | Previous Thread | Next Message | Previous Message ]


Replies:


VoyUser Login ] Not required to post.
Post a public reply to this message | Go post a new public message
* Notice: Posting problems? [ Click here ]
* HTML allowed in marked fields.
Message subject (required):

Name (required):

  Expression (Optional mood/title along with your name) Examples: (happy, sad, The Joyful, etc.) help)

  E-mail address (required):

* Type your message here:


Notice: Copies of your message may remain on this and other systems on internet. Please be respectful.

[ Contact Forum Admin ]


Forum timezone: GMT-5
VF Version: 2.94, ConfDB:
Before posting please read our privacy policy.
VoyForums(tm) is a Free Service from Voyager Info-Systems.
Copyright © 1998-2008 Voyager Info-Systems. All Rights Reserved.