Date Posted: 08:36 11/24/08 Mon
Author: Dean Austin
Subject: Re: Boiler room e.p.o. at door
In reply to: Howard Soli 's message, "Boiler room e.p.o. at door" on 18:27 09/17/08 Wed

>I don't know how I'm supposed to keep up with you
>inspection guys; the rules keep changing. The newest
>one that I'm hearing about is a "kill switch"
>requirement for a boiler at every doorway to the room.
> Is this true? If it is, where can I read about it?
>... If it is true, I want to find out if it's supposed
>to be series single poles, some 24v circuit to drop
>out the controller, etc.
>
>Thanks to anybody able to provide info.
The requirement for the emergency shut off located at the egress doors comes from the boiler rules. Location of the switches is determined by the boiler inspector not the electrical inspector. We can only inspect the wiring methods.

[ Next Thread | Previous Thread | Next Message | Previous Message ]

VoyUser Login ] Not required to post.
Post a public reply to this message | Go post a new public message
* Notice: Posting problems? [ Click here ]
* HTML allowed in marked fields.
Message subject (required):

Name (required):

  Expression (Optional mood/title along with your name) Examples: (happy, sad, The Joyful, etc.) help)

  E-mail address (required):

* Type your message here:


Notice: Copies of your message may remain on this and other systems on internet. Please be respectful.

[ Contact Forum Admin ]


Forum timezone: GMT-5
VF Version: 2.94, ConfDB:
Before posting please read our privacy policy.
VoyForums(tm) is a Free Service from Voyager Info-Systems.
Copyright © 1998-2008 Voyager Info-Systems. All Rights Reserved.